Introduction
Our galvanized calcium sulfate independent support network raised floor is engineered to perfection, catering to the sophisticated needs of modern commercial spaces. The core of the calcium sulfate composite network floor is crafted from top - grade, high - strength calcium sulfate boards. These boards not only serve as a robust foundation but also contribute significantly to the floor's fire - resistance and sound - insulation capabilities.
Surrounding the core, high - quality hot - dipped galvanized steel plates are expertly wrapped around the board core using specialized equipment. The galvanized steel plates are then firmly adhered to the surface of the core material with industrial - grade glue and permanently fixed through a hot - pressing process. This ensures a seamless and durable bond, enhancing the floor's overall strength and stability. Each floor panel is equipped with corner lock holes at its four corners. These lock holes play a pivotal role in the installation process, enabling a secure and tight fit between adjacent panels, thus creating a unified and stable flooring structure.
Features
1. Exceptional Load - Bearing Capacity and Performance
High Load - Bearing Capacity: Our floor exhibits an outstanding load - bearing capacity, capable of withstanding heavy loads from office furniture, equipment, and the continuous foot traffic in busy work environments. This high - strength performance ensures long - term durability without deformation or damage.
Superior Flatness: The manufacturing process adheres to strict quality control measures, resulting in a floor surface with remarkable flatness. This not only provides a comfortable walking experience but also ensures the stable placement of office furniture and equipment, minimizing the risk of tilting or uneven stress distribution.
Excellent Network Performance: Designed with the demands of modern office network wiring in mind, the floor offers a convenient and organized space for laying various cables, including power cables, data cables, and communication cables. This allows for efficient information transmission and seamless operation of office equipment.
2. Top - Tier Fire - Resistance
The calcium sulfate board core of our floor is classified as Class A non - combustible. In the event of a fire, it acts as a reliable firebreak, effectively preventing the spread of flames and heat. This high - level fire - resistance not only protects the building and its occupants but also provides valuable extra time for evacuation and fire - fighting efforts.
3. Unrivaled Stability in Diverse Environments
Whether faced with high - temperature, low - temperature, high - humidity, or low - humidity conditions, our galvanized calcium sulfate raised floor maintains exceptional stability. The unique combination of the calcium sulfate core and the galvanized steel plate structure renders it highly resistant to environmental changes. This means reduced risks of warping, swelling, or cracking, ensuring a long and trouble - free service life.
4. Enhanced Core Protection
The bottom layer of the floor consists of a galvanized steel plate, which serves a dual purpose. Firstly, it significantly enhances the overall strength of the floor, contributing to its high load - bearing capacity. Secondly, it acts as a protective shield for the calcium sulfate core, safeguarding it from moisture, corrosion, and physical damage. This added layer of protection further improves the durability and performance of the floor.
Technical data of Galvanized calcium sulfate network raised floor
No. |
Size |
Thickness |
Concentrated load
(deflection=2mm) |
Ultimated
load |
Uniform
load |
Rolling load |
Electrical
resistance |
(mm) |
(mm) |
lb |
N |
kg |
N |
N/m² |
N |
deflection |
Permanent
deformation |
(Ω) |
HP-G800 |
600×600 |
30/40 |
800 |
3550 |
363 |
10650 |
16500 |
2950 |
≤2mm |
≤0.5mm |
104-106 |
HP-G1000 |
600×600 |
32/40 |
1000 |
4450 |
454 |
13350 |
23000 |
3560 |
104-106 |
HP-G1250 |
600×600 |
32/40 |
1250 |
5560 |
567 |
16680 |
33000 |
4450 |
104-106 |
Flooring covering |
HPL,PVC or Ceramic tile |
Raised height |
From 100 to 1000mm, it need to be strengthen when raised height is greater than 1000mm. |
Electrical resistance |
It will be 104-106Ω when using the PVC coverings. |
Application
It is applicable to large office buildings, computer rooms, intelligent buildings, securities halls, government agencies, financial institutions, scientific research institutions, broadcasting centers, post and telecommunications, communication sites, telecommunications teaching, advertising printing, conference centers, media production, commercial websites, power and transportation, etc