Introduction
Our Anti-static Calcium Sulfate Raised Access Floor Panels are engineered with a high-strength calcium sulfate core, crafted through advanced manufacturing techniques to achieve optimal density and strength. This unique core design enables the panels to support heavy loads while maintaining a lightweight profile, ensuring effortless installation and handling.
For the top surface, we offer diverse material options to meet different needs. HPL delivers both durability and aesthetic versatility, while PVC provides superior anti-static performance, making it perfect for ESD-sensitive environments. Ceramic overlays, on the other hand, offer excellent impact resistance. The underside of the panels is protected by either aluminum foil for enhanced moisture and thermal insulation or galvanized steel sheets for added rigidity. Additionally, black PVC edge trim is applied to seal the edges, effectively preventing moisture penetration and extending the product lifespan.
Features
1. Heavy-duty & ESD Protection: Capable of supporting substantial equipment, these panels efficiently dissipate static electricity, making them an ideal choice for data centers and other high-tech facilities.
2. Fireproof Assurance: With a Class A non-combustible core, they offer enhanced fire safety, safeguarding critical spaces and valuable assets.
3. Precision & Interchangeability: Engineered with high accuracy, they ensure a seamless fit and easy replacement, simplifying installation and maintenance.
4. Sealed & Quiet Operation: The sealed edges keep out moisture and dust, while also reducing noise transmission between floors, creating a cleaner and quieter environment.
5. Eco-friendly Design: Manufactured from safe, eco-compliant materials, these panels align with green building standards, making them suitable for sustainable projects.
Technical data of ESD - Resistant Calcium Sulfate Access Floor
| No. |
Size |
Thickness |
Concentrated load
(deflection=2mm) |
Ultimated
load |
Uniform
load |
Rolling load |
Electrical
resistance |
| (mm) |
(mm) |
lb |
N |
kg |
N |
N/m² |
N |
deflection |
Permanent
deformation |
(Ω) |
| HP-G800 |
600×600 |
30/40 |
800 |
3550 |
363 |
10650 |
16500 |
2950 |
≤2mm |
≤0.5mm |
104-106 |
| HP-G1000 |
600×600 |
32/40 |
1000 |
4450 |
454 |
13350 |
23000 |
3560 |
104-106 |
| HP-G1250 |
600×600 |
32/40 |
1250 |
5560 |
567 |
16680 |
33000 |
4450 |
104-106 |
| Flooring covering |
HPL,PVC or Ceramic tile |
| Raised height |
From 100 to 1000mm, it need to be strengthen when raised height is greater than 1000mm. |
| Electrical resistance |
It will be 104-106Ω when using the PVC coverings. |
Application